Alternative BMS concept, modular Banks
#1
Hello to all,
My diy powerwall description is located here.
https://secondlifestorage.com/t-Grid-Tie...d-flexible


Defined as something modular and flexible I chose a different approach in organizing the cells.
The usual Pattern I see here is putting a load of cells together to an 1sxp block together, say a 1s80p. Then a couple, say 7, of these 1s80p blocks are connected in serial to a 7s80p. (Shown are 4 Blocks)



My approach described in above link is to block a number of cells, say 48, together as a 6s8p block.
(The Picture shows  3s2p Blocks).

 

This block has to be assumed for the moment ats being properly protected and balanced.
Building several of these I can put them in parallel, on the level of the positive and negative connector.
(Thats the status of the picture)

Having a modular system now. I can pull out any of the blocks at (nearly) any time, even under load, and the others will take up the load and continue to supply. By this I have easy manageable block sizes (in weight and in size), which can be pulled out and serviced quite easily, while the bulk of them are still in operation. I can start with a smaller block count and add more of them later, giving the chance going on-grid quite early and upgrading it step by step.


So far, so good. Now, how to solve the above mentioned protection and balancing of each single block? If I try to supply any sort of state-of-the-art balancing I have to provide that for each block, which is surely neither a simple nor a cheap solution.


Leaving all considerations aside which i have done to come ti this, pls think about the following.
  • I put a cheapo BMS without balancing to eack 6s8p Block. This BMS will check cell-exact the voltages and cut the supply out (for this block) on cell under- or overvoltage.
  • I connect all cell connection of same xs Level to a „Central point“, attaching a resistor of (say) 2 Ohms. This central point is in the main surveillance station of the whole pack, it is not near the cells.
  • From this „CP“ i cant connect to any cell level of all packs simultaneously, but only over the 2 Ohms resistors.
  • This CP provides a different type of „balancing“. Instead of surging an „Pack“ in the usual style, or a cell level in my modular struckture, i provied to supply that level with loading current.

What do I get now ?

  • All cells of same level are connected via the resistors. So they level out their voltages to the same level, assumed to the same SOC. (like all cell in an xp array)
  • All Modules (my structure) have a cheapo BMS to safety protect their cells.
  • All levels are connected to the Main control to being balanced from there, over the resistors. There is no surging BMS near the batteries, there is no heat near the batteries, there is no surging at all, no additional losses.
  • Balancing is done by charging a cell level, instad of discharging. That means it can and will be done any time i like, not (only) at top voltage level to prevent overcharging.
  • The connections between the modules run over resistors, which limit the currents, so i can use cheapo JST XH connectors, qualified for 3 Amps. Means I can (theoretically) charge quite more, because the current is distributed (supported by the resistors) over the blocks.
  • There are 2 possible reasons why I have to balance: The blocks are out of same SOC by history, or they contain bad cells surging power for their losses. The latter would cause the first as well. So, when I charge a Level/Block I target the possible reason for that directly. Otherwise I had to surge all other blocks for the same amount of energy …. and dissipate that.
  • When loading targets the questionable blocks/levels directly, a logfile about the balanced levels give significant info about seviceable levels.
  • when cells in one of my module heavily go out oft sync, the Module will be cut-off by the BMS. Surveillling the current of each block will show cuts-offs and point to Errors immediately. Pulling the block out gives an 6s8p array to be investigated (where only one p-row ist in question, regarding Balance protocols), which would give little problems.



So far, so good.
Question now from me, what do you specialist think of this approach? 
Any comments on safety, on efficiency, advantages and disadvantages ?
All comments welcome.
Reply
#2
I have many issues with the way things are done by powerwallers , but one thing I believe is correct is to have large banks of cells in parallel.

Once you get a few hundred wired into one 3.7 V unit , and a number of these in series to make your wall , there is no need for balancing , a voltmeter on each unit will show that capacity has ended up virtually the same in each parallel block , due to random selection of cells, and the voltage of all the packs stay very close ...

You say you can now easily remove parts for maintenance ...what maintenance ??? there should be none ... and how would you know if it was needed???

Putting resistors in is the last thing I would do ...they're wasting power and heating things up.
Reply
#3
I have a similar approach. I use a monitor not a BMS for now as my wall is only 4.6Kwh in size. I have small packs of 8 cells (1s8p) that are mounted to a back plane to make up 7s and multiple of these packs in parallel. I make the 8p packs in sets of 7 that as as close (tested before and after assembly) so when I install them in my wall the entire wall stays in balance.

This allows me to remove one packs or more and the wall stay running.

Now I only run my batteries from 4.1V to 3.6V and this negates any low or high cell issues as they seem to stay withing 10-30mV separated. I only notice any imbalance when the pack gets over the 4.1 per cell or below the 3.3V per cell.

When I do see one cell start to become too imbalanced I use a resistor Bank (3 Ohm 10W resistors for a 1A ish draw) to pull down the highest pack. This has only been needed twice as cell 7 was getting to 4.15 when the charging stopped. So I put 4 of these resistors on that one cell and brought it down to 4.0v (when removed the load to rested back at 4.11V) but the last time was about 3 months ago.
Reply
#4
(05-17-2018, 02:00 PM)ozz93666 Wrote: I have many issues with the way things are done by powerwallers , but one thing I believe is correct is to have large banks of cells in parallel.

Once you get a few hundred wired into one 3.7 V unit , and a number of these in series to make your wall , there is no need for balancing , a voltmeter on each unit will show that capacity has ended up virtually the same in each parallel  block , due to random selection of cells, and the voltage of all the packs stay very close ...

You say you can now easily remove parts for maintenance ...what maintenance ??? there should be none ... and how would you know if it was needed???

Putting resistors in is the last thing I would do ...they're wasting power and heating things up.

Oz, i didnt try to consider things "right" or "wrong". I am sure that the large banks structure has its features and advantages, otherwise it wouldnt be used so commonly.
I just try to make things different because it doesnt have some feature which I consider important for myself. I do not expect that everyone agrees.

Thanks for your input. Ill make my mind up regarding the losses of the resistors, which might show up dynamically during loading and unkoading. This is a loss which seem not to be present in thight connected banks, yet it might be it is hidden in the currents betweem cells which show different inner resistance. Very interesting point.

(05-17-2018, 02:40 PM)jdeadman Wrote: I have a similar approach.   I use a monitor not a BMS for now as my wall is only 4.6Kwh in size.   I have small packs of 8 cells (1s8p) that are mounted to a back plane to make up 7s and multiple of these packs in parallel.  I make the 8p packs in sets of 7 that as as close (tested before and after assembly) so when I install them in my wall the entire wall stays in balance.

This allows me to remove one packs or more and the wall stay running.    

Now I only run my batteries from 4.1V to 3.6V and this negates any low or high cell issues as they seem to stay withing 10-30mV separated.   I only notice any imbalance when the pack gets over the 4.1 per cell or below the 3.3V per cell.

When I do see one cell start to become too imbalanced I use a resistor Bank (3 Ohm 10W resistors for a 1A ish draw)  to pull down the highest pack.   This has only been needed twice as cell 7 was getting to 4.15 when the charging stopped.  So I put 4 of these resistors on that one cell and brought it down to 4.0v (when removed the load to rested back at 4.11V)    but the last time was about 3 months ago.
Very interesting. You are not so far away from my "modular" intentions. I already saw many times the advice not to use the full voltage swing, while people use different values for different reasons.
Can you tell what imbalances occur? Is it one cell being to high, or can it considered to be one too low ? I guest you use a fixed voltage to load, is that correct ? can you imagine to load the lowest pack instead of charging the highest?
Reply
#5
I have found some of my cell fuses to have broken due to flex in the bus bar. So basically my fault causing a decrease in capacity in that cell. So it would discharge quicker than the rest and then charge up faster. So I have just recently taken half of the wall own to test. Found my mistakes and 1 bad cell that I missed was a self discharging cell and replaced that one cell.

It's been great now that i re-installed that half and I have taken the other half off and I'm testing those packs for broken fuses and bad cells
Reply
#6
I have a build in progress with 2kWh modules that are 11s2p (LTO cells, 23.V nominal) and these are connected together via DB15 connectors through 0.27Ohm resistors and 3A Axial fuses. The reason for the low resistance permanently connected is the overall energy transfer on a 24x7 basis for packs that are "relatively" balanced the continuous flow should not be over 1A. The issue you may see on smaller packs is with high loads the packs may see larger voltage differentials appear under load and this will cause larger transfers to occur.





See my post in my LTO Powerwall for more info.

The downside for me is that I had to solder up 225 wires just for the pack connections and still have another 300 or so to go for the full setup and testing equipment, which I should have some images of in a couple of days.

Reply
#7
The way you describe what you want to do is pretty much the way I'm going to set mine up as.

Basically you are create "System Voltage Packs". Each pack runs at the system operating voltage. This allows for easy maintenance of any of the packs without disrupting the whole system.

With this setup, it is needed to have a bms control for each pack. But it needs to be very smart and adaptive, and can be synced with the other packs. Each pack will have it's own balancing board so the boards wouldn't need to have to handle 5A per pack per series in the pack. It could easily be 1A, so they could be small and efficient. Also easier to keep the packs in balance that way as well.

I'm currently working on this type of bms. I've ran into a few issues (mainly shorting out, programming errors, or bad contacts on the breadboard) that has set me back a little bit. I have new parts in the mail on the way here and continuing to work on the pcb design.

There are a few other designs I have in mind that I would like to implement in the system as I expand it's functionality. It takes time to build these things Tongue
Proceed with caution. Knowledge is Power! Literally! Cool 
Knowledge is Power; Absolute Knowledge is Absolutely Shocking!
Dollar Shave Club. Best Razor I've ever used
Certified 18650 Cell Reclamation Technician
Reply
#8
"It takes time to build these things" - so very, very true.

I have tried out cross connecting 2kWh packs (what would be adding in a pack after it has been out of service) with only 100mV difference for 11s2p (i.e. 26.1V connecting to 26.2V, they are LTO cells) and get 10A flowing. This made me realise I need to add in two volt meters to each pack that are visible when connecting/switching as a 3V difference would cause slight issues to say the least. From the test cell data a difference of 100mV per cell is 40A per cell for discharge, so 3V over 11s would end up with well over 80A flowing from the pack.

One volt meter for the cells and the other for the voltage on the other side of the breaker/switch - in your face readings and not via the computer AND then double check with a multimeter each time. I'm getting paranoid as the batteries have no "off" switch. Will have some more test readings soon and some pictures...

The DB15 connector is good for 5A per pin and I think it's 250V or 500V rated, but realistically at 5A I think it would melt the internal plastic... the cables sodlered to it are 0.75mm2 (24/0.2 stranded). Cheap, electrically proven since the 80's and can be locked in place with two screws.
Reply
#9
Hi completelycharged, hi Korishan, i see now that my idea of moduling and cross-connectiong is not so outrageous (and bad) as i was afraid of.

Very interesting infos, i will comment on them in detail, sorry at moment very busy.

(05-17-2018, 09:25 PM)completelycharged Wrote: I have a build in progress with 2kWh modules that are 11s2p (LTO cells, 23.V nominal) and these are connected together via DB15 connectors through 0.27Ohm resistors and 3A Axial fuses. The reason for the low resistance permanently connected is the overall energy transfer on a 24x7 basis for packs that are "relatively" balanced the continuous flow should not be over 1A. The issue you may see on smaller packs is with high loads the packs may see larger voltage differentials appear under load and this will cause larger transfers to occur.




Wonderful info. Your module size ist just 10 times of mine, and the reasons (and problems) of resistor in the crossconnections show up even more.
Sorry, i do not have at moment a circuitry CAD system running, so i refer to your plans.

I do not have fuses. My resistors are sitting directly at the pack. Thats saves some solder joints, but that is not the point. I think of being the resistors my fuses as well, since the will burn on a dangerous overload anyway. Since burned resistors or fuses are hardly detectable (by measuerment), i would prefer that these never burn at all, or at least only in safety situations.

For the size of the resistors, there seem to be taken in account different situations, normal use, plugging a relatively unbalanced pack to the live one and  the situation with a single bad cell.
Reply
#10
I personally like this approach. I am in a situation where I have reasonable quantities of different types of cells. 18650, 3000mAh pouches from newer laptops, 10,000 to 15,000 mAh pouch cells from eBikes, etc.

I am settling on the conclusion that I will need to build system-voltage packs of a single cell type, and then connect them all in parallel. This might also allow for a system of mixed chemistry, so long as the chosen system voltage range is acceptable - not part of my plans at the moment however.

I have also been thinking of building fully self contained SV packs and housing them in these... They are cheap, strong, kinda fire-proof and stackable. Dimensions are 32" x 11.25" x 6" which I figure provides enough volume for 3-4 kWh of cells and some BMS etc circuitry.

completelycharged, Cherry67, Korishan like this post
Reply


Who read this thread?
100 User(s) read this thread:
daromer (05-20-2018, 07:22 PM), Chris (07-14-2018, 09:47 AM), PaulKennett (05-17-2018, 11:54 PM), Joaquinsfy (05-20-2018, 06:09 AM), VdVoort4 (05-24-2018, 08:00 AM), Korishan (07-03-2018, 11:29 PM), A + A (07-04-2018, 07:08 AM), PAF (07-05-2018, 11:28 AM), Batrium (05-21-2018, 12:56 AM), ozz93666 (05-17-2018, 11:57 PM), BobinTN (07-06-2018, 04:46 PM), Mike C (05-21-2018, 03:16 AM), jdeadman (07-04-2018, 03:20 AM), wim (07-04-2018, 07:18 PM), typ49 (07-04-2018, 08:16 AM), watts-on (07-04-2018, 08:24 AM), jesusangel (07-05-2018, 03:28 PM), Hanssing (07-08-2018, 10:15 AM), Stefaan De Ridder (05-18-2018, 12:54 PM), tremors (05-17-2018, 10:14 PM), Johnny Stauersbøl (07-06-2018, 08:28 PM), ivnz (07-29-2018, 06:49 AM), Geek (07-04-2018, 12:31 AM), Dave Tucker II (05-17-2018, 04:49 PM), Rad (05-21-2018, 06:07 AM), SWEwall (05-20-2018, 07:44 PM), Jon (07-03-2018, 07:42 PM), floydR (07-04-2018, 02:03 AM), hookemdevils22 (09-10-2018, 04:32 PM), grgdgreek (05-20-2018, 10:34 AM), Reuse energy (05-21-2018, 10:40 AM), Grumplestiltskin (07-09-2018, 06:05 AM), 12ax7 (05-24-2018, 05:45 AM), ChrisD5710 (07-04-2018, 09:15 PM), Nikhil Mahajan (05-23-2018, 10:19 AM), CarelHassink (05-17-2018, 01:26 PM), garolittle (06-09-2018, 02:22 AM), Ste Collister (07-10-2018, 12:15 AM), Charly144 (07-04-2018, 06:36 AM), maunz (05-17-2018, 04:43 PM), BaronVonChickenPants (07-06-2018, 07:13 AM), Rookie (05-27-2018, 09:14 AM), acidice333 (05-17-2018, 07:48 PM), Jason Morris (07-04-2018, 03:17 AM), brwainer (07-05-2018, 10:21 PM), drchips (07-04-2018, 12:02 PM), Brent (07-14-2018, 11:51 PM), cat23 (07-03-2018, 08:17 PM), nrm21 (05-23-2018, 03:49 AM), rtgunner (07-10-2018, 04:17 AM), costty (05-19-2018, 06:13 AM), gpn (05-23-2018, 01:37 AM), alberta offgrid (05-18-2018, 02:18 AM), buffettdog (06-15-2018, 12:46 AM), John Allen (07-03-2018, 01:42 PM), thanar (05-17-2018, 03:05 PM), DK100 (05-21-2018, 07:43 AM), Matheus R. Costa (05-27-2018, 09:29 PM), DonaldBitterman (05-17-2018, 11:12 PM), Doyle (08-12-2018, 12:04 AM), Crimp Daddy (07-03-2018, 11:56 PM), Icy Strait (05-19-2018, 06:16 AM), Matman (05-17-2018, 11:24 PM), Redpacket (05-19-2018, 02:30 AM), velside (09-03-2018, 02:35 AM), cheamc (05-27-2018, 09:42 AM), EnergyDoc (10-15-2018, 12:44 AM), completelycharged (05-24-2018, 08:55 PM), Jonas Vanbeveren (06-14-2018, 12:34 PM), iomagico (05-24-2018, 10:40 AM), solar_18650 (05-24-2018, 07:32 PM), Curryx (05-22-2018, 03:43 PM), Halo.wings (05-18-2018, 08:01 PM), farmerjohn (05-17-2018, 03:19 PM), Michel (07-04-2018, 09:06 PM), Mathew Frank (07-04-2018, 01:17 PM), philsocal (07-26-2018, 03:15 PM), choncy12 (05-19-2018, 11:27 AM), Bubba (08-04-2018, 07:25 PM), GimmieDaGoodies (07-03-2018, 09:11 AM), MasterRadix (06-07-2018, 05:09 AM), Cherry67 (08-29-2018, 02:11 PM), michael620 (05-18-2018, 06:53 PM), redalertdt (05-20-2018, 01:27 AM), Sholphin02 (07-27-2018, 04:34 AM), Jason Turner (05-29-2018, 01:34 PM), Walde (07-28-2018, 08:46 AM), thlanaras (05-20-2018, 06:51 PM), Юрий Маркович (05-22-2018, 01:31 PM), Unleashed (05-31-2018, 12:38 PM), HWH (06-10-2018, 11:49 AM), David Leithoff (05-25-2018, 06:55 AM), Riplash (07-04-2018, 02:56 PM), m0hkw (05-29-2018, 02:20 PM), 100fuegos (06-02-2018, 10:12 AM), Ronnin (06-01-2018, 09:58 PM), cristi (06-06-2018, 03:05 PM), Jim Jr. (06-24-2018, 12:03 AM), bukvaahmed@gmail.com (10-06-2018, 10:53 AM), Bernard (06-16-2018, 02:56 AM)