Batrium: 2 Banks 1 BMS ?
#1
I plan on having two battery banks (Bank A and B) which have the capability to be run in parallel for maximum capacity.  But I also want to have the ability to isolate Bank A or B without having to take down the entire system for maintenance or other reasons.

Questions:

Can the Bartium system be setup to accommodate 2 banks.  If yes, can I have 2 shunts?

If I was to isolate Bank A, and the differential voltage started to increase between A and B, does the Bank with the higher voltage start to balance?

Last question, can I have more than 1 longmon per series string?  I suspect I might need more than 1 longmon to take care of a 320Ah pack.
Reply
#2
I think the current version can only handle 1 shunt.
You can make for isolations by using the relays to turn on/off contactors to disconnect a particular bank.
Longmons are per pack, not per series. So for a 14s string (48V nominal) you'd have 14 longmons.

I'm sure daromer will answer with more details later. Wink
Proceed with caution. Knowledge is Power! Literally! Cool 
Knowledge is Power; Absolute Knowledge is Absolutely Shocking!
Dollar Shave Club. Best Razor I've ever used
Certified 18650 Cell Reclamation Technician
Reply
#3
Perhaps it was just the way I was explaining it because I need to wire each cell from each series string in parallel. 

Remember, I am using EV cells which are formatted into a 5s module.  3 modules = 15s pack

[Image: bTLfQA3.jpg?1]

If I have 10 packs (1 pack = 3 modules) that I intend on splitting into two Banks of 5 packs, that would require 150 longmons in total if I don't wire each cell in parallel which would really easy to do because I have excellent access to the balance lead tabs of each cell.

So if I wire all the cells in parallel, I was hoping to cut down on the number of longmons required.  Perhaps 2 per parallel connection per bank...  I could always add more if needed but to be honest I would prefer to see if I can get away with less than 2.

Not really sure how flexible the BMS would be, but not being able to have 2 shunts is answering some questions already.
Reply
#4
I'm not sure if Jaron is working/planning on multiple shunts in the future. Might be a good idea to find that out first if you really need multiple ones.
Proceed with caution. Knowledge is Power! Literally! Cool 
Knowledge is Power; Absolute Knowledge is Absolutely Shocking!
Dollar Shave Club. Best Razor I've ever used
Certified 18650 Cell Reclamation Technician
Reply
#5
I can probably live without the 2nd shunt... or wire it in a way where I don't worry about the individual banks. I can always add a separate Victron shunt for State of Charge so really its not that big of a deal.

I still need to figure out the longmon situation... To simplify my question: Can you have more than 1 longmon per pack?
Reply
#6
(04-13-2018, 05:58 AM)Crimp Daddy Wrote: I can probably live without the 2nd shunt... or wire it in a way where I don't worry about the individual banks.  I can always add a separate Victron shunt for State of Charge so really its not that big of a deal.

I still need to figure out the longmon situation...  To simplify my question:  Can you have more than 1 longmon per pack?

You sure can, but not needed i thinks - if the longmons are accurate to 0.01v then one might turn on while other is off - if you have ocd that really messes with your brain!
Arrow Opus Dischargers - Definitely my choice pick for dischargershttp://amzn.to/2CmSpmj
Reply
#7
(04-13-2018, 06:11 AM)hbpowerwall Wrote:
(04-13-2018, 05:58 AM)Crimp Daddy Wrote: I can probably live without the 2nd shunt... or wire it in a way where I don't worry about the individual banks.  I can always add a separate Victron shunt for State of Charge so really its not that big of a deal.

I still need to figure out the longmon situation...  To simplify my question:  Can you have more than 1 longmon per pack?

You sure can, but not needed i thinks - if the longmons are accurate to 0.01v then one might turn on while other is off - if you have ocd that really messes with your brain!

That would most likely irritate me as I do have some OCD... like the good kind haha, but its still probably better than the pack going out of balance.

I think its worth mentioning that one "pack" for me is about 320Ah each if I split it into two banks, or 640Ah if I only make one.  I believe that is 3 times larger than what Batrium recommends per pack.

I guess it is all going to come down to how close each one of these cells are matched to one another.
Solexx X likes this post
Reply
#8
You cannot have 2 shunts in current version. You cannot have 2 separate systems on 1 Watchmon/master if you plan on using autolevel function since it will consider the whole chain and that will/can cause very odd behavior.

With that said there is work around and you potentially can have 2 banks totally sploit but you need to beware of the limitations.

If both those packs are in parallel in the end to the same input/output there is no problem. I have many of them.

Batrium max recommended is 400Ah per longmon. You can run 640 but it takes somewhat longer time to balance. You can also hook up 2 longmon per pack and double the balancing current. You can also as I said have 2 strings in parallel of 320Ah per string and 1 longmon per battery.

If you really consider having them as totally separated systems not hooked together at all consider 2 watchmons!
The Ultimate DIY Solar and build place
YouTube / Forum system setup / My webpage  Diy Tech & Repairs

Current: 10kW Mpp Hybrid | 4kW PIP4048 | 2x PCM60x | 83kWh LiFePo4 | 10kWh 14s 18650 |  66*260W Poly
Upcoming: 14S 18650~30kWh | Automatic trip breakers, and alot more
Reply


Who read this thread?
44 User(s) read this thread:
ANegron (04-22-2018, 02:23 PM), Dala (04-14-2018, 10:45 AM), mbrunton (Yesterday, 11:07 PM), rtgunner (04-13-2018, 01:19 AM), Farends (04-13-2018, 03:02 PM), cat23 (04-16-2018, 09:03 PM), drchips (04-13-2018, 02:31 PM), brwainer (04-15-2018, 06:26 AM), Jason Morris (04-13-2018, 04:17 AM), acidice333 (04-16-2018, 05:12 AM), DK100 (04-15-2018, 03:40 PM), Doyle (04-14-2018, 03:13 PM), farmerjohn (04-22-2018, 09:36 PM), colibri1 (04-20-2018, 06:29 PM), svdb92 (04-16-2018, 11:38 AM), Stephen Ryan (04-15-2018, 12:37 AM), Zvonko000 (04-15-2018, 02:32 PM), FilipII (04-13-2018, 04:49 PM), Redpacket (04-14-2018, 10:22 AM), John Southern (04-18-2018, 12:16 PM), Crimp Daddy (04-16-2018, 01:12 AM), Charly144 (04-15-2018, 06:28 PM), Solexx X (04-18-2018, 09:46 PM), The-J-Man (04-17-2018, 10:24 PM), wim (04-15-2018, 06:07 AM), jdeadman (04-15-2018, 11:44 PM), Mike C (04-16-2018, 01:26 AM), Frnandu Martiński (04-13-2018, 07:48 PM), PAF (04-15-2018, 06:03 PM), Korishan (04-15-2018, 11:59 AM), mike (04-13-2018, 01:14 PM), daromer (04-15-2018, 06:06 AM), watts-on (04-15-2018, 09:38 AM), Stefaan De Ridder (04-14-2018, 12:41 PM), CarelHassink (04-15-2018, 04:10 PM), aatheus (04-16-2018, 08:35 PM), floydR (04-15-2018, 05:05 PM), mr_hypno (04-13-2018, 03:53 PM), Jon (04-13-2018, 09:45 PM), Rad (04-13-2018, 12:54 AM), Dave Tucker II (04-23-2018, 01:24 AM), Geek (04-16-2018, 02:02 AM), Shade (04-15-2018, 01:40 PM), hbpowerwall (04-16-2018, 09:56 AM)