Conversol 5K-48 (same as pip 4048MS) error code 81

Daveyboy

Member
Joined
Aug 6, 2017
Messages
91
I've plugged my battery into this inverter for the fist time and i'm getting this error code. It's a continuous beep and the unit shuts off after about 10 seconds.

image_eklnns.jpg


It is a second hand machine, so has been set up before. I bought it from Conversol so I don't know what its last configuration was.

The manual says Error code 81 is "Host Data Loss", but I don't know what that means.

Anyone any idea? What is the host? Is it the computer with WatchPower on it? Or perhaps this unit was running in parallel and is expecting to see the first inverter in the string. There is no parallel card installed now, but there could have been one but removed.

My battery is at 58V and all connections are good after checking several times.

I'm reluctant to keep playing with things without asking first, because frankly, I'm scared of breaking it
 
Yes this error only appears explained in parallel guide so must be related with it.
http://www.mppsolar.com/manual/PIP-HS,MS (PF0.8)/PIP-HS_MS Parallel Guide.pdf
http://www.mppsolar.com/manual/PIP-HS,MS (PF0.8)/PIP-HS_MS Parallel Guide commissioning.jpg

There you have manual for parallel commissioning, maybe you can reverse the process.

If a non parallel unit shows 00 on screen after pressing enter button for 3 seconds before paralleling I think 00 must be non parallel mode instead of 28, SL, PAL or watever it shows.

Regards
 
jesusangel said:
Yes this error only appears explained in parallel guide so must be related with it.
http://www.mppsolar.com/manual/PIP-HS,MS (PF0.8)/PIP-HS_MS Parallel Guide.pdf
http://www.mppsolar.com/manual/PIP-HS,MS (PF0.8)/PIP-HS_MS Parallel Guide commissioning.jpg

There you have manual for parallel commissioning, maybe you can reverse the process.

If a non parallel unit shows 00 on screen after pressing enter button for 3 seconds before paralleling I think 00 must be non parallel mode instead of 28, SL, PAL or watever it shows.

Regards

Thank you kind sir!

That first link was just what I needed. It's out of parallel mode now. It had to be done on the inverter itself. WatchPower couldn't restore default settings.

Many Many Thanks!
Dave
 