if i build a battery pack of 18650's can i replace the 48V Battery in my UPS?

The Ups is an APC 2200VA ups with SLA batteries
Reply
#2
Many many many threads on this topic. Just search for the UPS in the thread title.

Yes you can replace them. Watch AveRageJoe on Youtube to get a full breakdown. He has a full system running on a SU3000 (or is it SUA).
Proceed with caution. Knowledge is Power! Literally! Cool 
Knowledge is Power; Absolute Knowledge is Absolutely Shocking!
Certified 18650 Cell Reclamation Technician

Please come join in general chit-chat and randomness at Discord Chat (channels: general, 3d-printing, linux&coding, 18650, humor, ...)
(this chat is not directly affiliated with SecondLifeStorage; VALID email req'd)

Kickstarter: Honest STM32F103 based dev Boards
Patreon: Korishan
Reply
#3
If you are going to be using the UPS as a UPS, please keep in mind that they keep their batteries fully charged which is good for Lead Acids, but not as great for Lithium Ion. Also, some have built-in non-customizeable equalization charges every 28 days or so. My suggestion would be to add one extra cell in series to lower the voltage. I have a 5000VA TripLite UPS that charges at 54.3V, which would be perfect for 13S (4.18V per cell), but I would run 14S to keep the cells at 80% charge. Also, 2200VA is almost 50 Amps at 48V. Make sure that you use a BMS that can handle it Most Chinese BMS's are way overrated and will tell you (buried in their details somewhere) that a 60A BMS can only handle 26 Amps!