completelycharged
Active member
- Joined
- Mar 7, 2018
- Messages
- 1,083
I have some solar panels that feed charge controllers at over 100V DC (4 panels in series and 2 or 3 strings in parallel) and to test out shading effects, etc. I added some additional breakers for each string as I had some "cheap $1 breakers"... with the intent of not using them as live switches as I had a separate DC rated breaker that I could use to switch off the HV side (should not do anyway), however I ended up being a bit lazy and switched one of the AC breakers when it was full sun.... aftere about a second of arcing internally I switched it back on... oops. damage done.
Ever since then the thing would trip "randomly" and after a period of time at high load.. so to carry on with an experiment I kept switching it back on each day (more than once on some days) and wondered if it would melt or set on fire (the wiring is all in a steel enclosure and I like experiments...) after a few months I thought it was time to see what the damage is as it never melted or set on fire.....
Interestingly ths was usually being tripped at about 110V and between 3-7A each time, so would have arced a bit on each trip and there is relatively little damage as I was expecting a bit more or a burn to the case !
Ever since then the thing would trip "randomly" and after a period of time at high load.. so to carry on with an experiment I kept switching it back on each day (more than once on some days) and wondered if it would melt or set on fire (the wiring is all in a steel enclosure and I like experiments...) after a few months I thought it was time to see what the damage is as it never melted or set on fire.....
Interestingly ths was usually being tripped at about 110V and between 3-7A each time, so would have arced a bit on each trip and there is relatively little damage as I was expecting a bit more or a burn to the case !